Fan tightness test for gas fire extinguishing installations BDS EN15004-1

Fan tightness test for gas fire extinguishing installations BDS EN15004-1

Testing the “tightness” of the room is vital to prove that the room protected by a gas fire extinguishing system is well sealed and the extinguishing agent will be retained for a sufficient period of time.
No matter how well a gas fire extinguishing system is designed, no matter how well it is executed, there is a factor that is not under the control of fire protection engineers. It is one of the common causes of system failure - the “tightness” of the room, i.e. its ability to retain the gas.
To ensure the effectiveness of your fire extinguishing system, testing the “tightness” of the protected room is vital to confirm that your protected area is well sealed and your gas extinguishing agent will not escape.

Environmentally friendly - no system emptying required
Prior to 1989, the emptying test was the only practical way to prove the ability of the protected room to retain the gas. Today, the generally accepted method of the VENTILATOR TIGHTNESS TEST is environmentally friendly. All standards – NFPA 2001, ISO 14520 and BDS EN 15004-1:2019 require the room “tightness” test as part of the approved procedures for all gas fire extinguishing systems.

Short duration
This means no loss of customer working time, as the total time for conducting the test is about 1 hour.

Recurring service
The service is recurring, allowing the room to be tested periodically, for example, if any changes are made to the room structure. A requirement of BDS EN 15004-1:2019 "Fixed fire extinguishing systems. Gaseous extinguishing systems. Part 1: Design, installation and maintenance" is that the test be performed every year, if it cannot be confirmed that there are no changes in the data since the last measurement.

Does not affect the fire extinguishing system
The test is multifaceted. Neither the extinguishing agent nor the construction of the fire extinguishing system precludes the need for the test.

An essential part of decommissioning Halon systems
New extinguishing agents have a lower tolerance for leakage than Halon systems. Rooms protected with Halon could lose up to 50% of the extinguishing agent concentration before the fire restarts. New extinguishing agents are more critical and can normally lose about 20% before re-ignition. For this reason, adequate sealing of the protected room using Halon will not be adequate when using another gas extinguishing agent.

                                  

How it works
For some gas fire extinguishing systems to be effective, the design concentration must first be reached and then maintained at the required levels inside the protected space. To achieve this, the space must be sealed at the external boundaries. The fan tightness test calculates the total area of ​​the gas leakage of the space and predicts how long it will take for the extinguishing agent and air mixture to maintain the required levels.

The test equipment consists of variable speed fans, expandable door panels, digital pressure gauges and specialist approved software.

The fan unit is mounted on the door of the protected space using expandable panels designed to fit most door sizes. By means of pressure and suction, the unit measures the size of the openings in the space through which the gas can escape.

The fan speed is adjusted to obtain a stable pressure between the test space and the surrounding spaces (equivalent to the column weight exerted by the extinguishing agent due to the system being emptied). This pressure is maintained until readings are taken from the manometers.

The measured amount of inlet air required to maintain this pressure level is equal to the amount leaking from the test area. The second measurement is made by performing the suction test. The two readings are averaged to reduce the degree of error.

The computer converts the flow and pressure readings into an Equivalent Leakage Area or the total area of ​​all cracks, gaps and holes in the test area. Using specific software, the data is processed according to methodologies approved by BDS EN 15004-1:2019 and NFPA 2001 to obtain the retention time of the agent concentration in the protected room. This retention time can be recalculated for different heights.

The computer software is designed to be conservative in its predictions. The software reproduces worst case scenarios - 50% of all cracks, gaps and holes in the test area are in the lower part, where the heavier gas and air mixture leaks, and 50% are in the upper part of the room, where the lighter air enters the test area. This approach makes the results extremely reliable and means that any system that passes the room ventilation test for tightness will also pass the full extinguishing agent emptying test.

Within an hour of completing the tests, the computer produces a printout with full details of the input and test results, and a little later - with a detailed report. Failure is indicated when the result of the Retention Time is less than ten minutes. However, if the ventilation test of the protected room shows an unsatisfactory result to the requirements of the standard, a detailed survey of the room is carried out, areas of leakage are noted, so that sealing work can be carried out.