Fire Control Panel FS6000
Description:FS6000 Addressable fire control panel
The FS6000 control panel has a modular organization. One Line Driver Module is capable to drive 4 output lines. Each output line may be configured as an open Line or two output lines may be united in a closed Loop configuration. The maximum configuration is of 16 Lines or 8 Loops.
Each Line or Loop may contain a maximum of 127 address point (detectors or adapters). The system registers the condition of the addressable points – normal, fire condition or fault condition – and the conditions are displayed at the panel with specific combinations of LEDs. For each addressable point a text message displayed on the panel to determine the point’s exact location may be assigned (example Floor 5 Room12). The communication between the panel and the addressable points is provided by two wire line and uses a specialized protocol. Protection against false alarm is available by repeated check ups of the activated detectors. The electromagnetic interference is filtered by the means of control equipment and software. In Loop configurations power is supplied from both sides and in case of a short circuit the short circuited segment is cut off by the isolators. All conditions and common faults are indicated and registered by the panel. It is possible to include conventional fire detectors in the FS6000 system using the addressable adapter.
The addressable adapter allows for conventional detectors to be included in the FS6000 Fire Alarm System.
Control, programming and signalization are carried out by the system’s front panel, supplied with LED indicators, liquid crystal display and a keypad. The language select option is user-friendly.
Technical data:
FIRE ALARM LINES
Maximum number of linear modules 4
Number of fire alarm lines (loops) in a module 4(2)
Maximum number of addresses in a line (loop) 127
Maximum resistance of the two-wire fire alarm line 40Ω
Output resistance 20Ω
FIRE ALARM AND INTERLOCKING OUTPUTS
Open collector type 30V/0.3A 8
Relay, potential-free, switching 250V/8A 10
Controllable, relay, potential (25-35)V (require end-of-line module) 2
FUNCTIONAL DESCRIPTION
Light indication for Test mode Green
Light indication for Night mode Red
Common purpose liquid crystal display 4 lines x 20 symbols
Built-in sound alarm for fire condition Two-tonal
Built-in sound alarm for fault condition One-tonal, discontinuous
Built-in real time clock Yes
Selection of test and setup modes Yes
Energy independent archive of events, registered by the system, containing event’s type, date and time 200 events
Communication interface for external devices RS 232
POWER SUPPLY
Mains 220V / 50Hz
Backup battery 24V / 7Ah
Consumption on battery < 400mA
Dimensions 360 x 490 x 110 mm
Weight (batteries not included) 10 kg