Addressable combined detector FD6120&6130L
Description:FD6120&6130L Combined optical smoke and rate of rise heat detector provides early warning of open or concealed fire condition responding to: smoke concentration threshold or rate of rise of the temperature higher than the specified one, or fixed temperature threshold. FD6120&6130L combine the advantages of optical smoke and rate of rise heat detectors with low delivery and installation expenses.
Technical data:
Operation Distraction of light (Tindal effect); Temperature rate of rise dependable electronic device
Operating voltage (15-30) VDC
Standby current 140 µA
Alarm state current 5 mA
Terminals Wire maximum cross section 1.5mm2
Degree of protection IP40
Operation temperature range Minus 10oC – 50oC
Sensitivity Complies with EN54-7 and EN54-5, class A2R
Mounting Contact base 3000
Dimensions (base included) Ø106 x 54 mm
Weight (base included) 0.170 kg
Protected area Circle with diameter 10m, h 8m