Interactive Fire Control Panel IFS 7002
Description:Interactive Fire Control Panel IFS7002
Basic features
- Fire Control Panel and all devices in the loops are fully programmable
- Two-way exchange of data between Fire Control Panel and connected in the lops devices
- Detection of Fault conditions: short circuit or interruption in a loop, removed fire detector or swapped fire detectors, connection of the loop to the grounds
- Two signal loops (branch lines are optional) for connecting of the fire detectors, input and/or output modules, adapters, automatic extinguisher modules
- One power loop for supplying of executive devices
- Automatic addressing of devices avoiding duplication of addresses
- Automatic detection of devices of the outputs
- Network operation of 128 Fire Control Panels and/or repeater panels
- Option for connection to dispatcher control point
- LED indication of the main events and conditions of the Fire Control Panel
- Built-in sounder
- LCD graphic display for visualization of text messages
- Touch screen panel
- Dialogue menus in language required by the customer
- Option for integration of a standard PC keyboard
- Built-in real time clock
Technical data
Fire alarm loops
- signal 2
- power 1
Addressable devices in one signal loop Up to 125
Cross section of the signal loop wire (0.8-2.5) mm2
Maximum resistance of the signal loop 100Ω
Number of devices in one branch Up to 32
Fire alarm zones Up to 250
Addressable devices in one zone Up to 60
Response time to activated detector signal Up to 10 seconds
Registered events by the counter of fire events Up to 9999
Archive of events Op to 1023
Power supply:
- mains 220/230VAC, 50/60Hz
- backup batteries 2x12 VDC, 18Ah
Current consumption of power supply loop Up to 1A
Outputs:
- relay 30VDC/1A 3
- controllable 28V DC/1A 2
- auxiliary supply 24VDC/1A 1
Interfaces:
- RS 232 or RS 485 1
- CAN 2
Dimensions 480 x 445 x 100 mm
Weight (batteries not included) 7.1 kg
Operating temperature Minus 5oC to 40oC
Relative humidity (93±3) % at 40oC
Degree of protection IP 40